How To Test Electrical Ring Main Circuits

The UK was the primary and is now power be the one nation on this planet which yet makes use of the 30 amp ring system for wiring socket shops in electrical installations. The ring fundamental circuit has extended been the topic of many heated dialogue between electrical consultants, still as an lineman you may little doubt want to check them in the middle of your duties. Right here is an outline of Ring Main review and examination procedures.

Warning- Please word that this can be a 'useless' check so the distribution board, shopper unit OR circuit have to be remoted from {the electrical} provide. To start with you may want to hold out a Secure Isolation Process and get permit to flash the provision.


How To Test Electrical Ring Main Circuits
How To Test Electrical Ring Main Circuits

This is the examination process:

Insulation Resistance

Disconnect all home equipment and equipment from the ring circuit and

perform insulation

checks between the Line, Impartial and Earth CPC.

Finish to

Finish Ring

Continuity Test

Set your check meter to low resistance vary and 'zero' the check leads. Measure the resistance of ring continuity of every of the reside, impartial and earth conductor ring loops. Document these finish to finish readings for future reference and acquiring into onto a check sheet. Notice that the place the earth conductors are smaller, the resistance will clearly be accumulated. For instance for twin and earth cables 1.5mm shall be 1.66 occasions accumulated than 2.5mm.

Tremendous Loop Test L&N

Cross join the reside and impartial conductors from reverse ends of the ring and to kind a brilliant loop. If ab initio this sounds complicated, strive drawing the reside and

impartial loops

of a hoop circuit on a chunk of paper with the alternative ends related. You will see that it kinds one large tremendous loop.

Test resistance between the ends you've got simply related collectively. The perusal taken between the tremendous loop ends ought to be about half that of your earlier continuity perusal. You possibly can then confirm the ring fundamental wiring and connections by going to every socket outlet and examination between reside and impartial. The place the socket is on the ring and the connections are 'good', your readings ought to be inside 0.05 of your unique tremendous loop perusal on the distribution board.

These readings commonly are not commonly recorded still will kind the premise in your evaluation of the ring fundamental circuit connections.

Excessive readings may point out that the socket is on a spur from the ring, that connections want tightening or that the socket is defective giving a poor connection to the plug and wishes changing. The place the readings commonly are not constant this point out that there are cross connections and the ring circuit has been bridged.

Tremendous Loop Test L&E

Cross join the road and earth conductors from reverse ends of the ring and to kind a brilliant loop. Test between the 2 units of ends you've got simply related collectively. The resistance perusal ought to be about half that of your earlier continuity perusal. You possibly can then confirm the ring fundamental wiring and connections by measure the resistance at every socket outlet as for Dwell and Impartial depicted beforehand. Testing between reside and earth on the sockets in addition checks for proper polarity.